3. Checking the power stage
The measurements described below are to be carried out only by
skilled specialists. Use a digital voltmeter. The measuring values
indicate the nominal value. If they are different from your measure-
ments, there is a defect.
3.1. Checking the mains rectifier
•
Disconnect the controller from the mains.
Caution!
Wait 5 minutes until the DC-bus is discharged no load!
•
Measure directly at the power terminals.
Measurement Measuring point Measuring value
Diodes in forward
direction
L1 
→
 +UG
L2 
→
 +UG
L3 
→
 +UG
-UG 
→
 L1
-UG 
→ 
L2
-UG 
→ 
L3
≈
 0.4V
≈
 0.4V
≈
 0.4V
≈
 0.4V
≈
 0.4V
≈
 0.4V
Diodes in reverse
direction
+UG 
→
 L1
+UG 
→ 
L2
+UG 
→ 
L3
L1 
→
 -UG
L2 
→
 -UG
L3 
→
 -UG
high resistance (OL)
high resistance (OL)
high resistance (OL)
high resistance (OL)
high resistance (OL)
high resistance (OL)
3.2. Checking the output stage
•
Disconnect the controller from the mains.
Caution!
Wait 5 minutes until the DC-bus is discharged!
•
Measure directly at the power terminals.
Measurement Measuring point Measuring value
Inverter diode in forward
direction
U 
→
 +UG
V 
→
 +UG
W 
→
 +UG
≈
 0.4V
≈
 0.4V
≈
 0.4V
Inverter diode in reverse
direction
UG 
→
 U
UG 
→ 
V
UG 
→ 
W
high resistance
high resistance
high resistance
Inverter diode in forward
direction
-UG 
→
 U
-UG 
→ 
V
-UG 
→ 
W
≈
 0.4V
≈
 0.4V
≈
 0.4V
Inverter diode in reverse
direction
U 
→
 -UG
V 
→
 -UG
W 
→
 -UG
high resistance
high resistance
high resistance