3. Checking the power stage
The measurements described below are to be carried out only by
skilled specialists. Use a digital voltmeter. The measuring values
indicate the nominal value. If they are different from your measure-
ments, there is a defect.
3.1. Checking the mains rectifier
Disconnect the controller from the mains.
Caution!
Wait 5 minutes until the DC-bus is discharged no load!
Measure directly at the power terminals.
Measurement Measuring point Measuring value
Diodes in forward
direction
L1
+UG
L2
+UG
L3
+UG
-UG
L1
-UG
L2
-UG
L3
0.4V
0.4V
0.4V
0.4V
0.4V
0.4V
Diodes in reverse
direction
+UG
L1
+UG
L2
+UG
L3
L1
-UG
L2
-UG
L3
-UG
high resistance (OL)
high resistance (OL)
high resistance (OL)
high resistance (OL)
high resistance (OL)
high resistance (OL)
3.2. Checking the output stage
Disconnect the controller from the mains.
Caution!
Wait 5 minutes until the DC-bus is discharged!
Measure directly at the power terminals.
Measurement Measuring point Measuring value
Inverter diode in forward
direction
U
+UG
V
+UG
W
+UG
0.4V
0.4V
0.4V
Inverter diode in reverse
direction
UG
U
UG
V
UG
W
high resistance
high resistance
high resistance
Inverter diode in forward
direction
-UG
U
-UG
V
-UG
W
0.4V
0.4V
0.4V
Inverter diode in reverse
direction
U
-UG
V
-UG
W
-UG
high resistance
high resistance
high resistance

Related product manuals