Installation
Electrical installation − Connections
4−11
L
EDB82MV752 EN 5.2
X3/ −4− Signal type Function Level
Lenze setting: Bold print
62 Analog output Output frequency 0 ... + 6 V
0 ... + 10 V
1)
7 GND1, reference potential for analog signals
8 Analog input
Act. or setpoint input
Change range using the DIP switch and C0034
Master voltage 0 ... +5 V
0 ... +10 V
−10 V ... +10 V
2)
Master current 0 ... +20 mA
+4 ... +20 mA
+4 ... +20 mA (open−circuit monitored)
9 Internal, stabilised DC voltage supply for setpoint potentiometer +5.2 V
20 Internal DC voltage supply for control of digital inputs and outputs +20 V 10 % (ref.: X3/7)
28
Digital inputs
Controller inhibit (CINH) 1 = START
E1
3)
Activation of JOG frequencies
JOG1 = 20 Hz
JOG2 = 30 Hz
JOG3 = 40 Hz
E1 E2
JOG1 1 0
E2
3)
JOG2 0 1
JOG3 1 1
E3 DC−injection brake (DCB) 1 = DCB
E4 Change of direction of rotation
CW/CCW rotation
E4
CW 0
CCW 1
39 GND2, reference potential for digital signals
A1
Digital output
Ready for operation with
internal supply:
external supply:
0 ... +20 V
0 ... +24 V
59 DC supply for X3/A1
internal (bridge to X3/20):
external:
+20 V
+24 V
1)
Output level 0 ... + 10 V: Adapt offset (C0109/C0422) and gain (C0108/C0420)
2)
Adjust offset (C0026) and gain (C0027) separately for each function module:
After replacing the function module or the basic device
After loading the Lenze setting
3)
Alternatively frequency input 0 ... 10 kHz single−tracked or 0 ...1 kHz double−tracked, configuration via C0425