Commissioning
V/f characteristic control
5−7
L
EDB82MV752 EN 5.2
1. Connect the keypad
2. Ensure that controller inhibit is active after mains connection
misc001
20 28
X3
}
Terminal X3/28 = LOW
3. Switch on the mains
ON
misc002
4. The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)
000
000
abcd e
mno
p
qr
Hi
Hz
Lo
1
j gfkih PS
0050
The USEr menu is active
5. Change to the mode to configure the basic settings for
your drive
000
000
a
bcd e
mno
p
qr
Hi
Hz
Lo
1
j gfkih PS
0050
z
y
wx
Blinking on the display: 0050
6. Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
7. Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
8. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f
[ H z ]
f
2
C 0 0 1 1
f
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
t
ir
C0011
f
2
f
1
t
ir
= acceleration time wanted
9. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
t
if
C0011
f
2
f
1
t
if
= deceleration time wanted
10. Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
100%
0
0 C0015
V
min
V
out
f
11. Set the V
min
boost (C0016)
Lenze setting: Depends on the controller type
The Lenze setting is suitable for all common
applications
12. If you want to change other settings, please go to the ALL
menu
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)
13. Go to the ALL menu
A Check the fan monitoring setting under code C0608:
for 8200 motec 0.25...0.37 kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may be
destroyed through overheating!
for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
14. Select the setpoint E.g. via potentiometer at
terminals 7, 8, 9
15. Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
16. The drive should now be running. If the drive does not start, press in
addition