Commissioning
Vector control
5−13
L
EDB82MV752 EN 5.2
15. Start the motor parameter identification (C0148) Only when the motor is cold!
A Ensure that the controller is inhibited
misc001
20 28
X3
}
Terminal X3/28 = LOW
B Set C0148 = 1 Press 
C Enable the controller
misc002
20
28
X3
Terminal X3/28 = HIGH
The identification starts:
The segment
is off
The motor consumes current and makes
a high−pitched" tone.
The motor does not rotate!
D If the segment becomes active after approx. 30 s,
inhibit the controller once again.
misc001
20 28
X3
}
Terminal X3/28 = LOW
Identification is completed.
Calculated and stored:
V/f rated frequency (C0015)
Slip compensation (C0021)
Motor stator inductance (C0092)
Measured and stored:
Motor stator resistance (C0084) = Total
resistance of motor cable and motor
16. If necessary, change other parameters Activate e.g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)
17. Go to the ALL menu
A Check the fan monitoring setting under code C0608:
for 8200 motec 0.25...0.37 kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may be
destroyed through overheating!
for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
18. Select the setpoint E.g. via potentiometer at
terminals 7, 8, 9
19. Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
20. The drive should now be running. If the drive does not start, press in