Function library
Selection of control mode, optimisation of operating behaviour
7−3
L EDB82MV752 EN 5.2
Application Operating mode
Single drives
Setting in C0014
recommended alternatively
With extremely alternating loads 4 2
With high starting duty 4 2
With speed control (speed feedback) 2 4
With high dynamic response (e. g. positioning and infeed drives) 2 −
With torque setpoint 5 −
With torque limitation (power control) 2 4
Three−phase AC reluctance motors 2 −
Three−phase sliding rotor motors 2 −
Three phase motors with assigned frequency−voltage characteristic 2 −
Pump and fan drives with square−law load characteristic 3 2 or 4
Group drives
(several motors connected to one controller)
Identical motors and identical loads 2 −
Different motors and/or changing loads 2 −
C0014 = 2: linear V/f characteristic control
C0014 = 3: square−law V/F characteristic control
C0014 = 4: vector control
C0014 = 5: sensorless torque control
) Note!
l Only change between the operating modes if the controller is inhibited!
l Do not use the operating mode "Torque control" for applications with power
control!
l Optimum drive behaviour in process controller applications, e.g. with speed
control or dancer position control can be achieved with the control modes "linear
V/f characteristic control" or with "vector control".
– If you need a high torque at low speed we recommend the operating mode
vector control".