Appendix
Code table
14−38
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0412
(cont.)
Analog signal source possible for C0412
7−57
0 Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module
1 Analog input 1 (AIN1−OUT)
X3/8 (Standard−I/O)
X3/1U or X3/1I (Application−I/O)
2 Frequency input (DFIN1−OUT) Observe C0410/24, C0425, C0426, C0427
3 Motor potentiometer (MPOT1−OUT)
4 (A) Analog input 2 (AIN2−OUT)
X3/2U or X3/2I
5 ... 9 Input signal is constantly 0 (FIXED0)
10 AIF input word 1 (AIF−IN.W1)
Only evaluated if C0001 = 3!
11 AIF input word 2 (AIF−IN.W2)
20 CAN−IN1.W1 or FIF−IN.W1
± 24000 ±480 Hz
2
14
100 % rated motor torque
21 CAN−IN1.W2 or FIF−IN.W2
22 CAN−IN1.W3 or FIF−IN.W3
23 CAN−IN1.W4 or FIF−IN.W4
30 CAN−IN2.W1
31 CAN−IN2.W2
32 CAN−IN2.W3
33 CAN−IN2.W4
200 Signals are assigned word by word from fieldbus
function module to FIF (e.g. INTERBUS or
PROFIBUS−DP)
See C0005
228 (A) PCTRL1−ACT
229 (A) PCTRL1−SET
230 (A) PCTRL1−OUT
231 (A) NSET1−RFG1−IN
232 (A) NSET1−NOUT
233 (A) PCTRL1−PID−OUT
234 (A) PCTRL1−NOUT
255 Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module
Either NSET1−N1 or NSET1−N2 active
C0413* Offset − analog
inputs
−200.0 {0.1 %} 200.0 The upper limit of the setpoint range from
C0034 corresponds to 100 %
7−34
1 AIN1−OFFSET 0.0 Setting for X3/8 or X3/1U, X3/1I
C0413/1 and C0026 are the same
2 AIN2−OFFSET 0.0 Setting for X3/2U, X3/2I
(only application I/O)
C0414* Gain − analog
inputs
−1500.0 {0.1 %} 1500.0 100.0 % = gain 1
Inverted setpoint selection through
negative gain and negative offset
1 AIN1−GAIN 100.0 Setting for X3/8 or X3/1U, X3/1I
C0414/1 and C0027 are the same
2 AIN2−GAIN 100.0 Setting for X3/2U, X3/2I
(only application I/O)