Connecon according to UL
The following data is valid for a three-phase mains connecon with 480 V.
Mains connecon with QUICKON connector
Motor MSEMA☐☐063-42 MSEMA☐☐080-32
Connecon X3
Connecon type QUICKON connector
cable cross‐secon
Typ. AWG 14 14
Min. AWG 16 16
Max. AWG 14 14
General UL notes
WARNING!
UL marking
Use 75 °C copper wire only, except for control circuits.
Maximum conductor size is AWG14.
Cord connected drives are for use only in NFPA 79 applicaons.
Overload protecon: 125 % of rated FLA
Integral solid state short circuit protecon does not provide branch circuit protecon. Branch circuit pro-
tecon must be provided in accordance with the Naonal Electrical Code and any addional local codes.
CAUTION - Risk of electric shock. Do not disconnect under load.
Marquage UL
Uliser exclusivement des conducteurs en cuivre 75 °C, sauf pour la pare commande.
Taille de conducteur maximale : AWG14.
Les entraînements avec câble d’alimentaon sont desnés exclusivement à des applicaons conformes à
la norme NFPA 79.
Protecon contre les surcharges : homologuée pour 125 % du courant assigné à pleine charge.
La protecon staque intégrée n’ore pas la même protecon qu’un disjoncteur. Une protecon par dis-
joncteur externe doit être fournie, conformément au Naonal Electrical Code et aux règlementaons
locales applicables.
ATTENTION ! Risque de choc électrique. Ne pas débrancher l’équipement sous charge.
Electrical installaon
Mains connecon
Connecon according to UL
63