EasyManua.ls Logo

Leuze electronic MSI-SR4B - Technical data

Leuze electronic MSI-SR4B
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Leuze electronic MSI-SR4B 23
13 Technical data
Table 13.1: Safety-relevant technical data
Table 13.2: Electrical data, protection rating, environment
Category acc. to EN ISO 13849-1: 2009 4
Performance Level (PL) in accordance with
EN ISO 13849-1: 2008
PL e
Category in accordance with EN ISO 13849-1 category 2
Probability of a dangerous failure per hour (PFH
D
) 2.0 x 10
-8
Mean time to dangerous failure (MTTF
d
) 73 years
Service life (T
M
) 20 years
B10
d
DC 13: 10.0 million switching cycles
AC 15: 1.4 million switching cycles
Stop category acc. to EN/IEC 60204-1 Stop 0
Operating voltage U
B
24 V AC/DC, 20%
Power consumption 3 W
External safeguarding for supply circuit 200 mA delay-action
Output contacts 3 normal open contacts, 1 normal closed contact
(Ag alloy)
Switching capacity of the contacts acc. to EN/
IEC 60947-5-1
AC-15: 230 V / 5 A 1.6x10
5
switching cycles
DC-13: 24 V / 3 A 1.3x10
5
switching cycles
Max. continuous current per current path 3 A
Ext. contact fuse protection per current path 5 A quick-action or 3.15 A delay-action
Max. switching frequency 3600 switching cycles/h
Mechanical life time 10 million switching cycles
Pickup delay, manual start 30 ms
Pickup delay, automatic start 300 ms
Regression delay, response time 10 ms
Max. test pulse acceptance 1 ms
Time window for signal sequence monitoring 20 ms
Control voltage/current on S12, S22, S31 24 V DC / 40 mA
Max. input current 100 mA
Admissible input line resistance < 30
Operating temperature 0° … +55°C
Storage temperature - 25° … +70°C
Overvoltage category in accordance with
VDE 0110 part 1
III for rating voltage 300 V AC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com