Product Data
Table 3: Single Zone Art Cool Mirror Wall Mount Electrical Data.
Electrical Data
ELECTRICAL DATA
Indoor Unit Outdoor Unit Hertz Voltage
Voltage
Range
(Min. to
Max.)
MCA MOP
Com-
pressor
Quantity
LRA
Compressor Motor
RLA
Outdoor Fan
Motor
Indoor Fan
Motor
Cooling Heating
W FLA W FLA
LAN090HSV5 LSU090HSV5
60 208 - 230 187 - 253
10.0 15.0 1 7.5 7.0 7.0 43 0.4 30 0.4
LAN120HSV5 LSU120HSV5 10.0 15.0 1 7.5 7.0 7.0 43 0.4 30 0.4
LAN181HSV5 LSU181HSV5 19.0 30.0 1 17.0 12.6 14.3 124 0.78 70 0.4
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
W: Fan Motor Rated Output (W)
LRA = Locked Rotor Amps