20 | PRODUCT DATA
Single Zone Art Cool
TM
Mirror Wall Mount Engineering Manual
Model
Sound Pressure Levels (dB[A])
Cooling (Max) Heating (Max.)
LSU090HSV5 47 51
LSU120HSV5 47 51
LSU181HSV5 55 55
Table 7: Art Cool Mirror Outdoor Unit Acoustic Data
Figure 14: Outdoor Unit Sound Level Measurement.
Outdoor Unit Sound Pressure Level Measurement
Outdoor Unit Sound Pressure Levels
ACOUSTIC DATA
Outdoor Units
Measurements are taken 3.3 ft away from the front of the unit.
Sound pressure levels are measured in dB(A) with a tolerance of ±1.
Data is valid at nominal operation conditions. Operating conditions
are assumed to be standard.
Reference acoustic pressure 0dB=20μPa
Sound pressure levels are tested in an anechoic chamber under ISO
Standard 3745, and may be different according to the test condition
or equipment.
Sound level will vary depending on a range of factors including the
construction (acoustic absorption coefficient) of a particular room in
which the unit was installed.
Figure 15: LSU090/120HSV5 Cooling Sound Pressure Level Diagram.
Figure 16: LSU090/120HSV5 Heating Sound Pressure Level Diagram.
LSU090HSV5/ LSU120HSV5 Cooling and Heating Sound Pressure Diagrams