EasyManua.ls Logo

LG ARTCOOL LA090CP - Art Cool Quick Reference: Electrical & Refrigerant

LG ARTCOOL LA090CP
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
25' maximum
8' minimum
12' maximum
OIL TRAP
INDOOR UNIT
OUTDOOR UNIT
***Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement:
For systems with maximum elevation of 25 ft. (see Figure A), refrigerant lines must be oil
trapped between 8 ft. and 12 ft. of elevation.
For systems with elevation of greater than 25 ft. Refrigerant lines must be oil trapped at least
every 12 ft. of elevation.
* Each system should have a 6-8 inch inverted trap at the condensing unit if mounted above
indoor unit.
Figure A.
Example: 25 ft. maximum elevation.
ART COOL MINI-SPLIT SINGLE ZONE
ELECTRICAL & REFRIGERATION QUICK REFERENCE
NOTE: Recommend shielded cable for low voltage wiring.
Please see local electrical codes for proper wire specifications.
All equipment single phase.
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
Wire Size
Minimum AWG 14-3
Indoor/Outdoor Connecting Cable Shielded 18-4
Refrigerant Line Specifications***
Electrical Specifications
Type Model BTUs Voltage Rated Amps MCA* MOP**
ARTCOOL Indoor Outdoor
A/C LA090CP 9,000 36V DC 115 7.2 15 15
A/C
LA120CP 12,000
36V DC 115 9.3 15 20
A/C
LA121CPM 11,500
36V DC 115 10.5 15 20
A/C
LA180CP 18,000
36V DC 230/208 9.8 15 20
H/P
LA090HP 9,000
36V DC 115 7.2 15 20
H/P
LA120HP 12,000
36V DC 115 9.3 15 20
H/P LA121HPM 11,500 36V DC 115 10.5 15 20
Type Model BTUs Pipe Size Additional Max. Pipe Max.
ARTCOOL
Liquid Suction Refrigerant Length
Elevation
A/C LA090CP 9,000 1/4" 3/8" 0.21 oz./ft. 50' 25'
A/C LA120CP 12,000 1/4" 1/2" 0.21 oz./ft. 50' 25'
A/C LA121CPM 11,500 1/4" 1/2" 0.21 oz./ft. 50' 25'
A/C LA180CP 18,000 1/4" 1/2" 0.21 oz./ft. 100' 50'
H/P LA090HP 9,000 1/4" 3/8" 0.21 oz./ft. 50' 25'
H/P LA120HP 12,000 1/4" 1/2 " 0.21 oz./ft. 50' 25'
H/P
LA121HP 11,500 1/4" 1/2 " 0.21 oz./ft. 50' 25'
Single Zone
Single Zone

Related product manuals