***Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement:
For systems with elevation of 25 ft. (see figure A), refrigerant lines must be oil trapped
between 8 ft. and 12 ft. of elevation.
For systems with elevation of greater than 25 ft. Refrigerant lines must be oil trapped at
least every 12 ft. of elevation.
* Each system should have a 6-8 inch inverted trap at the condensing unit if mounted above
indoor unit.
17
Mini-Split
Standard
Single Zone
Type
A/C
A/C
A/C
A/C
A/C
H/P
H/P
H/P
H/P
H/P
System Model #
LS090CP
LS120CP 
LS180CP 
LS240CP 
LS302CP 
LS090HP
LS120HP 
LS180HP 
LS240HP 
LS302HP 
Indoor
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
BTUs
9,000
11,500
18,000
22,500
28,000
9,800
11,500
19,500
22,500
28,000
Rated 
Amps
7.0 
10.5 
8.6/9.5 
11.5/12.5 
14.5/15.6 
10.5 
10.5 
11.5/12.5 
11.5/13.0 
14.5/15.6 
MCA*
15 
15 
15 
20 
25 
15 
15 
20 
20 
25
MOP**
15
25
20
30
30
25
30
30
30
30
Electrical Specifications
Outdoor
115
115
230/208
230/208
230/208
115
115
230/208
230/208
230/208
Voltage
All equipment single phase.
NOTE: Recommend shielded cable for low voltage wiring.
Please see local electrical codes for proper wire specifications.
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
***For LS180HP, LS240CP/HP, LS302CP/HP
Wire Size
Minimum AWG  14-3
12-3***
Indoor/Outdoor Connecting Cable Shielded 18-4
Mini Split 
Standard
Single Zone
Type
A/C
A/C
A/C
A/C
A/C
H/P
H/P
H/P
H/P
H/P
System 
Model #
LS090CP
LS120CP 
LS180CP 
LS240CP 
LS302CP
LS090HP
LS120HP 
LS180HP 
LS240HP 
LS302HP 
Pipe size
Liquid Suction
1/4" 3/8"
1/4" 1/2 "
1/4" 1/2 "
1/4" 5/8"
1/4" 5/8"
1/4" 1/2"
1/4" 1/2 "
1/4" 5/8 "
1/4" 5/8"
1/4" 5/8"
BTUs
9,000
11,500
18,000
22,500
28,000
9,000
11,500
19,500
22,500
28,000
Additional
Refrigerant
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.35 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.25 oz./ft.
0.35 oz./ft.
Max. length 
each pipe
50'
50'
100'
100'
100'
50'
50'
100'
100'
100'
Max.
elevation
25'
25'
50'
50'
50'
25'
25'
50'
50'
50'
Refrigerant Line & Formula Specifications***
MINI-SPLIT STANDARD SINGLE ZONE
ELECTRICAL & REFRIGERATION• QUICK REFERENCE
Figure A.
Example: 25 ft. maximum elevation.
Must install trap inverted.