- 11 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 2 Functions & Controls
2.3 Healthy Dehumidification operation
When the dehumidification operation is set by the remote controller, the intake air temperature is detected and the set-
ting temp. is automatically set according to the intake air temperature.
When intake air temp. is 1 C above the setting temp., condition of compressor is same as in cooling mode operation.
When intake air temperature reaches 1 C below the setting temp., compressor operates in step1~step3 and the indoor
fan speed again operates at low speed or comes to a stop.
2.4 Automatic operation
When the Auto operation is set by the remote controller, the intake air temperature is detected and the setting temp. is
automatically set according to the intake air temperature and operation mode.
The air volume is automatically set according to the intake air temperature.
2.5 Auto changeover operation
The air conditioner changes the operation mode automatically to keep indoor temperature.
When room temperature vary over ±2°C with respect to setting temperature, air conditioner keeps the room tempera-
ture in ±2°C with respect to setting temperature by changing the mode from cooling to heating and vice versa.
Intake air Temp. Setting Temp.
26°C intake air temp. 25°C
24°C intake air temp.< 26°C intake air temp. -1°C
22°C intake air temp. < 24°C intake air temp. -0.5°C
18°C intake air temp. < 22°C intake air temp.
intake air temp. < 18°C18°C
+0.5°C
-0.5°C
-2°C
+4°C
+2°C
Cooling thermo off
Heating thermo off
Switching point
Switching point
Setting
Temp.
Cooling
operation
Heating operation
Cooling
operation
Mode