- 18 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 2 Functions & Controls
5.1 Five Seconds Stand-by (fan)
Prevention fan in indoor unit rotate after 5 seconds when unit is turned on.
5.2 Two Minutes Stand-by (comp.)
Compressor starts two minutes later, after it is turned off
5.3 Hot start
When unit starts in the heating mode to prevent cold wind blowing, the indoor fan does not rotate until the temp. of
heat exchanger reaches 30°C(model by model)
5.4 Freeze prevention (Protection of the evaporator pipe from frosting)
If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in cooling cycle
operation mode, compressor, outdoor fan are turned off.
When indoor pipe temp. is 7°C or higher after 2 min pause of compressor compressor, outdoor fan is turned on
NOTE: Some Models are different by T1.
5. Protection Functions & Controls
Comp. free
Comp. Step 4
Comp. Step 2
Comp. off
T1
3˚C
6˚C
7˚C
Indoor pipe
temp.
T1: 0 ~ 2°C