-25-
• Wrap the area which accommodates the rear piping
housing section with vinyl tape.
• Bundle the piping and drain hose together by wrap-
ping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.
3) Connection of the pipes-Outdoor
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
GAS LIQUID
Capacity
(Btu/h)
Refrigerant
7K, 8K, 9K 3/8"[4.2kg.m] 1/4"[1.8kg.m]
R-22
11K, 12K, 14K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
7K~14K 3/8"[4.2kg.m] 1/4"[1.8kg.m] R-410A
Pipe Size[Torque]