80 2005 Product Data
9. Coefficient of Capacity Change
(A)
(A)
Indoor
Indoor
Outdoor
Outdoor
Classification
Height
(A)
The Coefficient of Capacity Change
Total Pipe Length(m)
5 7.5 10 12.5 15
- - - 0.94 0.93
- 0.97 0.96 0.95 0.94
0.99 0.98 0.97 0.96 0.95
1.0 0.99 0.98 0.97 0.96
1.0 0.99 0.98 0.97 0.96
0.99 0.98 0.97 0.96 0.95
- 0.97 0.96 0.95 0.94
- - - 0.94 0.93
10
7
5
0
0
5
7
10
Model: 18K~24K Btu Heat Pump
Capacity
(Btu/h)
7k~12k
3/8"(Ø9.52)
1/2"(Ø12.7)
1/2"(Ø12.7)
5/8"(Ø15.88)
5/8"(Ø15.88)
5/8"(Ø15.88)
3/4"(Ø19.05)
1/4"(Ø6.35)
1/4"(Ø6.35)
1/4"(Ø6.35)
1/4"(Ø6.35)
3/8"(Ø9.52)
3/8"(Ø9.52)
3/8"(Ø9.52)
4 or 7.5
4 or 7.5
4 or 7.5
4 or 7.5
4 or 7.5
7.5
7.5
7
7
15
15
15
15
15
15
15
30
30
30
30
30
20
20
20
20
30
30
50
18k~24k
30k~36k
Pipe Size
Gas Liquid
Standard
Length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Piping length and elevation