Service Manual 61
Troubleshooting Guide
7
Supplied power is not normal
Indoor/outdoor fan is locked
Too much refrigerant
Defect in current sensing circuit in outdoor pcb assembly
Over current Error
(CT2)
Supplied voltage to
Outdoor pcb is about
AC 220/240V ?
Does indoor / outdoor fan work
normally ?
YES
No
Check power source
No
Check indoor / outdoor fan and
adjust.
Check flow
Refrigerant pressure is right ?
YES
No
Check refrigerant pressure
and adjust.
Current sensing circuit is right ?
YES
No
Check current sensing circuit.
- check CT is damaged in outdoor pcb
(output wire is disconnected to pin or not)
- BD01N is inserted in right position
(refer marking on pcb and component)
- Spec of R01N (1k), R02N (1.65k) is correct
- Direction of diode (D01N, D02N) is right
Description Cause of error