EasyManua.ls Logo

LG AUUW24GD2 - Connecting Copper Pipes; Preparation of Piping

LG AUUW24GD2
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting Copper Pipes
Preparation of Piping
Main cause of gas leakage is defect in flaring
work. Carry out correct flaring work in the
following procedure.
Cut the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor
and the outdoor unit.
• Cut the pipes a little longer than measured
distance.
Cut the cable 1.5m longer than the pipe
length.
Burrs removal
• Completely remove all burrs from the cut
cross section of pipe/tube.
Put the end of the copper tubing to downward
direction as you remove burrs in order to
avoid to let burrs drop in the tubing.
Putting nut on
• Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring work)
Flaring work
Carry out flaring work using dedicated
flaring tool for R410A as shown below.
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the
flared section and do flaring work again.
Installation Manual 11
ENGLISH
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Inclined
Inside is shining without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Bar
Copper pipe
"A"
<Wing nut type>
<Clutch type>
Pipe diameter
Inch (mm)
A inch (mm)
Wing nut type Clutch type
Ø 1/4 (Ø 6.35)
0.04~0.07
(1.1~1.8)
0~0.02
(0~0.5)
Ø 3/8 (Ø 9.52)
Ø 1/2 (Ø 12.7)
Ø 5/8 (Ø 15.88)
Connecting Copper Pipes

Related product manuals