Single CAC Outdoor Unit
9. Electric Characteristics
94
Standard Inverter
Outdoor Unit Combined Indoor Unit Unit Power Comp OFM IFM
Model names Model Name
No. of
Unit
Phase
Hz
Volts
Voltage
range
MCA MFA MSC RLA kW FLA kW FLA
AUUW09GA0
[UU09W UL0]
ATNH09GRLE2
[CT09 NR2]
1
1
50
220-240
Min. : 198
Max. : 264
6.9 15 - 5.00 0.043 0.25 0.020 0.40
ABNW09GL2A2
[CB09L N22]
7.3 15 - 5.00 0.043 0.25 0.095 0.80
AVNH09GELA2
[CV09 NE2]
6.9 15 - 5.00 0.043 0.25 0.030 0.40
AQNH09GALA0
[CQ09 NA0]
7.1 15 - 5.00 0.043 0.25 0.020 0.60
AUUW12GA0
[UU12W UL0]
ATNH12GRLE2
[CT12 NR2]
7.9 15 - 5.80 0.043 0.25 0.020 0.40
ABNH12GL2A2
[CB12L N22]
8.3 15 - 5.80 0.043 0.25 0.095 0.80
AVNH12GELA2
[CV12 NE2]
7.9 15 - 5.80 0.043 0.25 0.040 0.40
AQNH12GALA0
[CQ12 NA0]
8.1 15 - 5.80 0.043 0.25 0.030 0.60
AUUW18GAE
[UU18W UE4]
ATNW18GQLA0
[CT18 NQ4]
16.2 20 - 12.40 0.085 0.33 0.040 0.40
ABNW18GM1A0
[CM18 N14]
16.2 20 - 12.40 0.085 0.33 0.080 0.40
ABNH18GL2A2
[CB18 N22]
16.6 20 - 12.40 0.085 0.33 0.120 0.80
UVNH18GJLA2
[CV18 NJ2]
16.2 20 - 12.40 0.085 0.33 0.050 0.40
AQNH18GALA0
[CQ18 NA0]
16.5 20 - 12.40 0.085 0.33 0.040 0.70
AUUW24GAE
[UU24W U44]
ATNW24GPLA0
[CT24 NP4]
22.3 30 - 17.00 0.124 0.48 0.060 0.60
ABNW24GM1A0
[CM24 N14]
22.2 30 - 17.00 0.124 0.48 0.090 0.50
ABNH24GL3A2
[CB24L N32]
22.7 30 - 17.00 0.124 0.48 0.150 1.00
UVNH24GJLA2
[CV24 NJ2]
22.3 30 - 17.00 0.124 0.48 0.060 0.60
AUUW30GAE
[UU30W U44]
ATNW30GPLA0
[UT30 NP4]
22.3 30 - 17.00 0.124 0.48 0.080 0.60
ABNW30GM1A0
[UM30 N14]
22.5 30 - 17.00 0.124 0.48 0.150 0.80
UVNH30GJLA2
[UV30 NJ2]
22.3 30 - 17.00 0.124 0.48 0.060 0.60
AJNW30GVLA0
[UJ30 NV2]
22.3 30 - 17.00 0.124 0.48 0.160 0.60
AUUW366D2
[UU36W UO2]
ATNH36GNLE2
[UT36 NN2]
22.4 40 - 16.93 0.171 0.65 0.140 0.60
ABNW36GM2A0
[UM36 N24]
23.1 40 - 16.93 0.171 0.65 0.210 1.30
UVNH36GKLA2
[UV36 NK2]
22.5 40 - 16.93 0.171 0.65 0.090 0.70
AJNW36GVLA1
[UJ36 NV3]
22.4
40 - 16.93 0.171 0.65 0.160 0.60
Note
1. Voltage supplied to the unit terminals should be within the minimum and
maximum range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM and IFM are measured as the outdoor unit test condition.
6. Select the wire size based on the MCA.
7. MFA is used to select the circuit breaker and ground fault circuit
interrupter, and recommended circuit breaker type is ELCB(Earth Leakage
Circuit Breaker).
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes (A)
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)