2. Specifications
11
Single CAC Outdoor Unit
Standard Inverter
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power levIndoorel is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. This product contains Fluorinated greenhouse gases.
Combination
Outdoor unit
AUUW24GAE
[UU24W U44]
AUUW24GAE
[UU24W U44]
Indoor unit
ATNW24GPLA0
[CT24 NP4]
ABNW24GM1A0
[CM24 N14]
Capacity
Cooling
Min.~Rated~Max. kW 2.84 ~ 6.80 ~ 7.80 2.80 ~ 6.80 ~ 7.48
Min.~Rated~Max. Btu/h 9,700 ~ 23,200 ~ 26,600 9,500 ~ 23,200 ~ 25,500
Heating
Min.~Rated~Max. kW 3.20 ~ 8.00 ~ 8.80 3.20 ~ 7.50 ~ 8.25
Min.~Rated~Max. Btu/h 10,900 ~ 27,300 ~ 30,000 10,900 ~ 25,600 ~ 28,100
Power Input
Cooling Rated kW 2.00 2.07
Heating Rated kW 2.22 2.34
Running Current
Cooling Rated A 8.90 9.10
Heating Rated A 9.70 10.30
SEER / SCOP Wh / Wh 6.80 / 4.20 6.10 / 3.90
Seasonal Energy Label
(A++ to E Scale)
Cooling / Heating - A++ / A+ A++ / A
Annual Energy Consumption Cooling / Heating kWh 350 / 2,110 390 / 2,154
Combination
Outdoor unit
AUUW24GAE
[UU24W U44]
AUUW24GAE
[UU24W U44]
Indoor unit
ABNH24GL3A2
[CB24L N32]
UVNH24GJLA2
[CV24 NJ2]
Capacity
Cooling
Min.~Rated~Max. kW 4.00 ~ 7.10 ~ 7.70 2.80 ~ 6.80 ~ 7.48
Min.~Rated~Max. Btu/h 13,600 ~ 24,200 ~ 26,300 9,500 ~ 23,200 ~ 25,500
Heating
Min.~Rated~Max. kW 2.00 ~ 7.50 ~ 8.25 3.08 ~ 7.50 ~ 8.25
Min.~Rated~Max. Btu/h 6,800 ~ 25,600 ~ 28,100 10,500 ~ 25,600 ~ 28,100
Power Input
Cooling Rated kW 2.36 2.25
Heating Rated kW 2.05 2.45
Running Current
Cooling Rated A 10.4 9.90
Heating Rated A 9.00 10.8
SEER / SCOP Wh / Wh 5.60 / 3.90 5.80 / 3.90
Seasonal Energy Label
(A++ to E Scale)
Cooling / Heating - A+ / A A+ / A
Annual Energy Consumption Cooling / Heating kWh 444 / 2,082 410 / 2,154