2. Specifications
13
Single CAC Outdoor Unit
Standard Inverter
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power levIndoorel is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions :
*Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
*Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. This product contains Fluorinated greenhouse gases.
Combination
Outdoor unit
AUUW366D2
[UU36W UO2]
AUUW366D2
[UU36W UO2]
Indoor unit
ATNH36GNLE2
[UT36 NN2]
ABNW36GM2A0
[UM36 N24]
Capacity
Cooling
Min.~Rated~Max. kW 4.00 ~ 10.0 ~ 11.0 4.00 ~ 10.0 ~ 11.0
Min.~Rated~Max. Btu/h 13,600 ~ 34,100 ~ 37,500 13,600 ~ 34,100 ~ 37,500
Heating
Min.~Rated~Max. kW 4.40 ~ 11.0 ~ 12.1 4.50 ~ 11.2 ~ 12.3
Min.~Rated~Max. Btu/h 15,000 ~ 37,500 ~ 41,300 15,400 ~ 38,200 ~ 42,000
Power Input
Cooling Rated kW 2.82 3.12
Heating Rated kW 3.09 3.19
Running Current
Cooling Rated A 12.30 13.60
Heating Rated A 13.40 13.90
SEER / SCOP Wh / Wh 5.41 / 3.81 5.11 / 3.81
Seasonal Energy Label
(A++ to E Scale)
Cooling / Heating - A / A A / A
Annual Energy Consumption Cooling / Heating kWh 648 / 2,800 685 / 2,866
Combination
Outdoor unit
AUUW366D2
[UU36W UO2]
AUUW366D2
[UU36W UO2]
Indoor unit
UVNH36GKLA2
[UV36 NK2]
AJNW36GVLA1
[UJ36 NV3]
Capacity
Cooling
Min.~Rated~Max. kW 3.80 ~ 9.50 ~ 10.5 4.00 ~ 9.50 ~ 10.50
Min.~Rated~Max. Btu/h 13,000 ~ 32,400 ~ 35,800 13,600 ~ 32,400 ~ 35,800
Heating
Min.~Rated~Max. kW 4.20 ~ 10.5 ~ 11.6 4.40 ~ 10.50 ~ 11.50
Min.~Rated~Max. Btu/h 14,300 ~ 35,800 ~ 39,600 15,000 ~ 35,800 ~ 39,200
Power Input
Cooling Rated kW 2.78 2.79
Heating Rated kW 3.08 3.27
Running Current
Cooling Rated A 12.10 12.10
Heating Rated A 13.40 13.40
SEER / SCOP Wh / Wh 5.11 / 3.81 5.41 / 3.81
Seasonal Energy Label
(A++ to E Scale)
Cooling / Heating - A / A A / A
Annual Energy Consumption Cooling / Heating kWh 652 / 2,800 615 / 2,505