[Air inlet side view]
The power cord connected to the outdoor unit 
should be complied with the following specifications 
(Rubber insulation, type H05RN-F approved by HAR 
 or SAA).
The connecting cable connected to the indoor and 
outdoor unit should be complied with the following 
specifications (Rubber insulation, type H05RN-F 
approved by HAR or SAA).
CAUTION
8.5mm
20mm
GN/YL
7.5mm
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
 (18K/24K/28K/36K)
1.25mm
2
 (48K)
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
2
 (18K/24K/28K/36K)
3.5mm
2
 (48K)
Control box cover
Indoor 
power cord
Remote 
controller
cord
Control box cover
Terminal Block of Outdoor Unit
1(L) 2(N) 3 4 5 1(L) 2(N) 3 4 5
Terminal Block of Outdoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Indoor Unit
Terminal Block of Indoor Unit
POWER INPUT
RSTN
POWER INPUT
RSTN
1(L) 2(N) 3 4 5
Terminal Block of Indoor Unit
3(L) 4(N)
567
1(L) 2(N) 3(L) 4(N)
5678
Terminal Block of Outdoor Unit
Power Cord
Terminal Block of Indoor Unit
3(L) 4(N)
567
1(L) 2(N) 3(L) 4(N)
56
Terminal Block of Outdoor Unit
Power Cord
■ 
18K/24K/28K Btu
■ 36K/48K Btu
• Heat Pump Model
• Cooling Model
• Heat Pump Model
• Cooling Model