Dehumidifier
SERVICE MANUAL
MODEL: DHA1260HR/HL
DHA1660HR/HL
CAUTION
- BEFORE SERVICING THE UNIT,
READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
- ONLY FOR AUTHORIZED SERVICE.
website http://www.lgservice.com
e-mail http://www.lgeservice.com/techsup.html

Questions and Answers

  • J
    Joseph CrawfordJul 31, 2025
    What to do if my LG Other dehumidifier does not operate?
    • A
      Anna HarperJul 31, 2025
      If your LG dehumidifier isn't working (neither the compressor nor the fan motor starts), here's what you can check: * **Power Supply:** Ensure the outlet has power. * **Plug Contact:** Make sure the plug is properly installed in the outlet, or replace it. * **Bucket:** If the Auto Shut Off light is on, empty the bucket. * **Humidity Control:** Turn the humidity control switch towards Max. * **Wiring:** Check for disconnected or loose wires, referring to the wiring diagram to connect or repair them.
  • P
    Patricia SmithAug 9, 2025
    Why is my LG DHA1260HL Other dehumidifier so noisy?
    • D
      deborah33Aug 9, 2025
      There are several reasons why your LG dehumidifier might be operating noisily: * **Fan Issues:** If the fan is cracked, out of balance, or partially missing, replace it. * **Foreign Material:** Check for and remove any foreign material causing a rattle. * **Tube Contact:** Adjust the tubing if it's hitting the frame. * **Fan Blade Contact:** Check the motor mount and tighten it if the fan blade is hitting the frame. * **Compressor Noise:** Internal compressor noise may require replacing the compressor. * **Loose Screws:** Tighten any loose set screws. * **Motor Assembly Bearings:** If the motor assembly bearings are worn, replace the motor if knocking sounds continue or if it's loose. Replace the entire motor assembly if it hums or the noise appears internal.
  • A
    Anna RobertsAug 17, 2025
    What to do if my LG DHA1260HL is dripping water?
    • N
      Nathaniel StoneAug 17, 2025
      If your LG dehumidifier is dripping water, here are a few things to check: * **Bucket Installation:** Ensure the bucket is correctly positioned on the drain pan hangers. * **Drain Hose Connection:** Inspect the drain hose connection and repair if needed. * **Bucket Condition:** Replace the bucket if there's a leak. * **Bucket Removal:** Turn off the unit before removing the bucket to empty it. * **Bucket Overflow:** Check the micro switch if the bucket overflows.
  • R
    richardoneillAug 21, 2025
    Why is my LG DHA1260HL dehumidifier not dehumidifying enough?
    • T
      Tony SpencerAug 21, 2025
      If your LG dehumidifier isn't dehumidifying sufficiently, consider these points: * **Low Relative Humidity:** If the relative humidity is low, turn off the dehumidifier. * **Poor Air Circulation:** Ensure the dehumidifier has free and unobstructed air circulation by moving it to a better location. * **Clogged Assembly:** Clean the evaporator and/or condenser assembly if it's clogged with dust and dirt. * **Dirty Air Filter:** Clean the air filter. * **Motor Assembly Issues:** Check, repair, or replace the motor assembly if it's not operating correctly.
  • S
    Samantha SanchezAug 27, 2025
    What to do if the thermostat does not start in my LG DHA1260HL?
    • M
      Mackenzie RitterAug 27, 2025
      If the thermostat in your LG dehumidifier doesn't start, check the thermostat and replace it if it's defective.
  • M
    Maria MooreNov 3, 2025
    Why does my LG DHA1260HL Other compressor cycle on the overload protector?
    • R
      Ricky MejiaNov 3, 2025
      Your LG dehumidifier's compressor might be cycling on the overload protector due to several reasons: * **Voltage Issues:** The line voltage may be too high or too low. It should be between 198V and 264V. If the voltage is intermittent, you may need a new power supply. * **Air Circulation:** Poor air circulation can cause this issue. Ensure the dehumidifier has free and unobstructed airflow. * **Dirty Assembly:** The H/E assembly might be clogged with dust or dirt. Clean the assembly. * **Motor Assembly:** If the motor assembly isn't running, determine the cause and replace if necessary. * **PTC Assembly:** Check and repair the P.T.C. assembly if it's bad. * **Electrical Issues:** Look for short circuits or grounds in the electrical circuit and repair them. * **Pressure Equal...
  • C
    Colleen DanielsNov 12, 2025
    What to do if the motor assembly runs but the compressor does not run on my LG DHA1260HL?
    • B
      bowersmichaelNov 12, 2025
      If the motor assembly runs but the compressor doesn't on your LG dehumidifier, consider the following: * **Voltage:** The voltage must be between 198V and 264V. If it's outside these limits, consult an electrician. * **Wiring:** Check the wire connections. Repair or replace any loose terminals. If wires are disconnected, refer to the wiring diagram for identification and reconnect them. Also, ensure the wire connections match the wiring diagram. * **Rotary Switch:** Check the rotary switch for continuity, using the wiring diagram for terminal identification. Replace the switch if the circuit is open. * **Compressor:** Check the compressor for an open circuit or ground. If found, replace the compressor. * **Overload Protector (O.L.P.):** If the compressor has an externally mounte...

Summary

1. PREFACE

1.1 SAFETY PRECAUTIONS

Essential safety guidelines for servicing, including power disconnection and plug integrity.

1.4 SPECIFICATIONS

Detailed technical specifications including capacity, power, refrigerant, and component details.

1.5 CONTROL

Humidity Control

Explains how to set and use the humidity control for desired moisture levels.

1.6 HOW TO OPERATE DEHUMIDIFIER

1.6.5 HUMIDISTAT

Details the humidistat's role in maintaining constant relative humidity.

2. CIRCUIT DIAGRAM

3. DISASSEMBLY INSTRUCTIONS

3.2.10 COMPRESSOR

Detailed steps for discharging refrigerant and removing the compressor.

3.3 REFRIGERATING CYCLE

Overview of the refrigeration cycle components and their interconnections.

3.3.1 CONDENSER ASSEMBLY AND EVAPORATOR ASSEMBLY(HEAT EXCHANGE ASSEMBLY)

Steps to remove the condenser and evaporator assemblies.

3.3.2 CAPILLARY TUBE ASSEMBLY

Procedure for removing the capillary tube assembly.

3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM

Detailed procedure for discharging, evacuating, and recharging the refrigerant system.

4. TROUBLESHOOTING GUIDE

Dehumidifier Does Not Run

Troubleshooting steps when the dehumidifier fails to operate.

Cannot Dehumidify

Diagnosing issues when the unit is not effectively dehumidifying.

Dehumidifier Does Not Operate (Both compressor and fan motor do not operate.)

Troubleshooting no power, poor plug contact, full bucket, or loose wiring.

Motor Assembly Runs but Compressor Does Not Run

Diagnosing issues with voltage, wiring, rotary switch, compressor, or O.L.P.

Compressor Cycles on Overload Protector (O.L.P.)

Troubleshooting compressor cycling due to voltage, air circulation, or component failure.