Part 2 Functions & Controls
Cooling & heating Opeattions
6.1.1 Cooling Mode
Setting
Temp.
-0.5°C.
+0.5°C.
Comp. OFF
Comp. ON Comp. OFF Comp. ON
INV. Comp.
Frequency
Constant
Comp.
Low
High Low
Thermo.
ON
Thermo
OFF
High
Operating frequency of compressor depends on the load condition, like the difference between the room temp. and
the set temp., frequency restrictions.
If the compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30
seconds. ( not emergency conditions)
Compressor turned off when
- intake air temperature is in between ±0.5°C of the setting temp. limit for three minutes continuously.
- intake air temperature reaches below 1.0°C of the temperature of setting temp..
Compressors two minutes time delay.
- After compressor off, the compressor can restart minimum 2 minutes later.