- 81 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
5. Trouble Shooting
LEV Openness
(Pulse)
COMP Frequency
(Hz)
Toff(105) °C
T1(90) °C
T2(95) °C
OFFNormal
OFF ControlNormal
Normal
Normal
D-Pipe temp.
32
33
D-pipe (Inverter)
temp. high
(105°C
)
D-pipe (Constant)
temp. high
(105°C
)
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
Check the discharge pipe sensor for INV.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Check the discharge pipe sensor for Cons.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Display
code
Title Cause of error Check point & Normal condition
Check Point
CH 32
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
CH 33
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
4. Check the constant compressor. (same with CH21)