8 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
Piping length and the elevation
CAUTION:
• If 48k Model is installed at a distance of 15m, 450g of refrigerant
should be added (15-7.5) x 60g = 450g
• Capacity is based on standard length and maximun allowance length
is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.