8 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 5m
30
35
30
40
50
60
90
Capacity
Gas
5/8"
5/8"
5/8"
5/8"
3/4"
3/4"
3/4"
Liquid
1/4"
1/4"
1/4"
1/4"
3/8"
3/8"
1/2"
Elevation B(m)
Length A(m)
*Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
7.5
7.5
7.5
7.5
7.5
7.5
7.5
Standard
5
5
5
5
5
5
5
Max.
30
30
30
30
30
30
30
Max.
15
15
15
15
15
15
15
18K BTU/h
24K BTU/h
30K BTU/h
36K BTU/h
42K BTU/h
48K BTU/h
60K BTU/h
CAUTION:
If 48k Model is installed at a distance of 15m, 450g of refrigerant
should be added (15-7.5) x 60g = 450g
Capacity is based on standard length and maximun allowance length
is on the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.