11
ELECTRICAL WIRING
INDOOR UNIT
• Remove the control box cover for
electrical connection between the
indoor and outdoor unit.(Remove two
screws ➀.)
• Use the cord clamper to fix the cord.
Perform the electrical wiring work according to
the electrical wiring connection.
• All wiring must comply with local
requirements.
• Select a power source that is capable of
supplying the current required by the air
conditioner.
• Use a recognized circuit breaker
between the power source and the unit.
A disconnection device to adequately
disconnect all supply lines must be
fitted.
• Capacity of circuit breaker
WIRING CONNECTION
OUTDOOR UNIT
• Remove the control cover for wiring
connection.
• Use the cord clamper to fix the cord.
• Earthing work
Connect the cable of diameter 1.6mm
2
or more to the earthing terminal
provided in the control box and do
earthing.
Please check !!
Capacity 1 Phase 3 Phase
18K BTU/h 20A -
24K BTU/h 25A -
30K BTU/h 25A -
36K BTU/h 35A 25A
42K BTU/h 40A -
48K BTU/h - 25A
60K BTU/h - 25A