GENERAL DATA
Type Single Zone 2 x 2 Four-Way Ceiling Cassette
System (Model) (Indoor Unit / Outdoor Unit)
LC098HV4
(LCN098HV4 / LUU097HV)
LC128HV4
(LCN128HV4 / LUU127HV)
LC188HV4
(LCN188HV4 / LUU189HV)
Ceiling Grille Model Number (Sold Separately) PT-UQC / PT-QCHW0 PT-UQC / PT-QCHW0 PT-UQC / PT-QCHW0
Cooling Capacity (Min/Rated/Max) (Btu/h)
3,600 ~ 9,000 ~ 9,900 3,400 ~ 11,100 ~ 12,400 7,700 ~ 18,000 ~ 24,800
Cooling Power Input
1
(kW)
0.19 ~ 0.66 ~ 0.83 0.25 ~ 0.88 ~ 1.1 0.54 ~ 1.44 ~ 2.60
EER2 (OD 95°F)
13.65 12.6 12.5
SEER2
20.2 19.4 20.5
Heating Capacity (Min/Rated/Max) (Btu/h)
4,400 ~ 11,000 ~ 12,100 2,800 ~ 14,000 ~ 15,500 6,500 ~ 18,500 ~ 23,400
Heating Power Input
1
(kW)
0.15 ~ 0.83 ~ 1.05 0.22 ~ 1.19 ~ 1.5 0.50 ~ 1.95 ~ 2.60
COP (OD 47°F)
3.88 3.44 2.78
HSPF2
10.55 10.35 9.70
Rated Low Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB)
7,000 9,100 12,700
Low COP (OD 17°F)
2.92 2.7 2.45
Maximum Heating Capacity (Btu/h)
Outdoor 17°F (DB)/Indoor 70°F (DB)
11,000 11,900 17,000
Outdoor 5°F (DB)/Indoor 70°F (DB)
10,100 10,700 16,200
Outdoor -4°F (DB)/Indoor 70°F (DB)
9,040 9,280 15,250
Power Supply V, Ø, Hz
2
208-230 / 1 / 60
Outdoor Unit Operating Range
Cooling (°F DB)
0 to +118
6
0 to +118
6
5 to +118
6
Heating (°F WB)
-4 to +64 -4 to +64 -4 to +64
Indoor Unit Operating Range
Cooling (°F WB)
57 to 77 57 to 77 57 to 77
Heating (°F DB)
59 to 81 59 to 81 59 to 81
Indoor Temperature Setting Range
Cooling (°F DB)
65 to 86 65 to 86 65 to 86
Heating (°F WB)
61 to 86 61 to 86 61 to 86
Unit Data
Refrigerant Type
3
/ Refrigerant Control
R410A / EEV
Indoor Unit Sound Pressure Level ±1 dB(A) (H/M/L)
4
36 / 33 / 30 38 / 35 / 32 41 / 39 / 36
Outdoor Unit Sound Pressure Level ±1 dB(A) (Cool/Heat)
4
47 / 51 49 / 52 48 / 52
Indoor Unit Net / Shipping Weight (lbs.)
31 / 37 31 / 37 31.5 / 40.0
Outdoor Unit Net / Shipping Weight (lbs.)
82 / 89 82 / 89 127.8 / 140.0
Grille Net / Shipping Weight (lbs.)
7 / 9 7 / 9 7 / 9
Power Wiring / Communications Cable (No. x AWG)
2
4 x 14 4 x 14 4 x 14
Compressor (Type x Qty.)
Twin Rotary x 1 Twin Rotary x 1 Twin Rotary x 1
Dehumidification Rate (pts./hr.)
1.6 2.47 3.3
Fan
Indoor Unit Type x Qty. / Outdoor Unit Type x Qty.
Turbo x 1 / Axial x 1
Motor / Drive
Brushless Digitally Controlled / Direct
Airflow Rate
Indoor Unit (H / M / L [CFM])
300 / 265 / 230 335 / 283 / 247 460 / 424 / 388
Outdoor Unit (CFM)
988 988 2,048
Piping
Liquid (in.)
Connection Size
1/4 1/4
Pipe Size
1/4 3/8
Vapor (in.)
Connection Size
3/8 1/2
Pipe Size
3/8 5/8
Indoor Unit Condensate Drain O.D. / I.D. (in.)
1-1/4 / 1 1-1/4 / 1
Additional Refrigerant Charge (oz./ft.)
0.22 0.43
Maximum Pipe Length (ft.)
66 164
Piping Length
5
(no additional refrigerant, ft.)
24.6 24.6
Maximum Elevation Difference (ft.)
49 98.4
Table 2: Four-Way 2 x 2 Ceiling Cassette System General Data.
EEV: Electronic Expansion Valve, IDU: Indoor Unit, ODU: Outdoor Unit. Unit comes with a dry helium charge.
This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb
(WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb
(WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2
All power wiring/communication cables from ODU to IDU are field supplied and are to be minimum 14
AWG, 4-conductor, stranded, shielded or unshielded (if shielded, must be grounded to chassis at ODU
only), and must comply with applicable local and national codes.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
Piping lengths are equivalent.
6
Cooling range can be extended from 0°F or 5°F down to -4°F using the Low Ambient Wind Baffle Kit
(sold separately).