6-4 REFRIGERATION CYCLE
6-4-1 Cleaning
There is no need for routine condenser cleaning in normal Home operating environments. If the environment is particularly
greasy or dusty, or there is significant pet traffic in the home, the condenser should be cleaned every 2 to 3 months to
ensure maximum efficiency.
If you need to clean the condenser:
Remove the mechanical cover.
Use a vacuum cleaner with a soft brush to clean the grille, the open areas behind the grille and the front surface area of
the condenser.
Replace the mechanical cover.
- 23 -
Troubleshooting Chart
PARTIAL Freezer Low flowing sound of A little higher • Refrigerant level is low due
LEAKAGE compartment and Refrigerant is heard and than ambient to a leak.
Refrigerator don't frost forms in inlet only. temperature. • Normal cooling is possible by
cool normally. restoring the normal amount of
refrigerant and repairing the leak.
COMPLETE Freezer Flowing sound of refrigerant Equal to ambient • No discharging of Refrigerant.
LEAKAGE compartment and is not heard and frost isn't temperature. • Normal cooling is possible by
Refrigerator don't formed. restoring the normal amount of
cool normally. refrigerant and repairing the leak.
PARTIAL Freezer Flowing sound of refrigerant A little higher • Normal discharging of the
CLOG compartment and is heard and frost forms than ambient refrigerant.
Refrigerator don't in inlet only. temperature. • The capillary tube is faulty.
cool normally.
WHOLE
Freezer
Flowing sound of refrigerant Equal to ambient • Normal discharging of the
CLOG
compartment and
is not heard and frost isn't temperature. Refrigerant.
Refrigerator don't cool.
formed.
MOISTURE Cooling operation Flowing sound of refrigerant Lower than • Cooling operation restarts
CLOG stops periodically. is not heard and frost melts. ambient when heating the inlet of the
temperature. capillary tube.
COMP- Freezer and Low flowing sound of A little higher • Low pressure at high side
RESSION Refrigerator refrigerant is heard and than ambient of compressor due to low
don't cool. frost forms in inlet only. temperature. refrigerant level.
NO COMP- No compressing Flowing sound of refrigerant Equal to ambient • No pressure in the high
RESSION operation. is not heard and there is temperature. pressure part of the
no frost. compressor.
CAUSE
TEMPERATURE
OF THE
COMPRESSOR
REMARKS
STATE OF
THE UNIT
STATE OF THE
EVAPORATOR
LEAKAGE
CLOGGED BY DUST
DEFECTIVE
COMPRESSION
www.Appliantology.org