Model
Room Air Room Air LP070HM* LP090HM* LP120HM* LP150HM*
Dry Wet Temperature Across Temperature Across Temperature Across Temperature Across
Bulb Bulb Indoor Coil (∆ T) Indoor Coil (∆ T) Indoor Coil (∆ T)
Indoor Coil (∆ T)
Min Max Min Max Min Max Min Max
Rating Btu/h 6200 6400 8200 8400 10900 11200 13300 13500
Rating CFM 220 250 260 290 330 360 350 390
85 22 24 24 27 27 30 28 30
80 23 24 25 28 28 31 29 31
50 75 24 25 26 29 29 32 30 31
70 26 27 28 30 31 34 32 33
65 26 27 28 30 31 34 32 33
85 19 22 22 24 24 29 27 30
80 20 23 23 25 25 29 28 31
45 75 21 24 24 26 26 30 29 31
70 22 24 24 27 27 31 30 32
65 23 25 25 28 28 32 31 33
85 17 20 20 22 23 27 27 30
80 18 21 21 23 23 28 28 31
40 75 19 22 22 24 24 29 29 31
70 20 23 23 24 25 29 30 32
65 21 24 24 25 26 30 31 33
85 15 17 17 20 21 24 27 29
80 16 18 18 21 22 25 28 30
35 75 17 19 19 22 23 26 29 31
70 18 20 20 23 23 27 30 31
65 19 21 21 24 24 28 31
32
Heating Change of Temperature - Heat Pumps