TROUBLE DIAGNOSIS
-62-
Problems Causes Checks Measures Remarks
High  Cycle pipe is clogged. Check sequence. - Maybe evacuate should be the first  Direr must be replaced.
temperature in 1. Check temperature of condenser step here. If the servicer puts a torch 
the freezer manually. to a charged system, the joint will
compartment. If it is warm, OK. explode and spray refrigerant on him. 
If it is not, compressor discharging Also, if oil is forced out, it could  
joints might be clogged. create a fire or safety hazard.
2. Manually check whether hot line - If it's warm, OK. If it's not, 
pipe is warm. condenser discharging line weld 
If it is warm, OK. joints might be clogged.
If it is not, condenser outlet weld  Discharge the system and recover the 
joints might be colgged. refrigerant. Then use a torch to 
disconnect unbraze the piping to repair
the obstruction. Repair, evacuate the 
system, and recharge it before testing. 
Leak at loop pipe weld joint Check sequence. Replace the compressor, weld,  Drier must be replaced.
(discharge) in compressor. 1. Manually check whether  evacuate, and recharge refrigerant.
condenser is warm, It is not warm 
and the frost forms partly on the 
evaporator in the freezer 
compartment.
Faulty cooling fan in the compressor  Check sequence. - Replace if motor does not operate.
compartment. 1. Check cooling fan operation. - If fan is disconnected, check fan
2. Check that cooling fan is  damage and reassemble it.
disconnected from the motor. ■ Refer to fan motor disassembly 
and assembly sequence.