- 10 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
• LV-B1861HL
• LV-B1864HL
• LV-B2461HL
• LV-B2464HL/LV-B2464BL
• LV-H246BLA0
For installation over rated distance, 30g of refrigerant should be added for each meter.
ex) When installed at a distance of 15m, 300g of refrigerant should be added.
(15-5) x 30g = 300g
Pipe size(Diameter: ) Piping length(m) Elevation(m)
MODEL
Gas Liquid Rated Max Rated Max
LV-B1861HL 1/2" 1/4" 5 15 5 8
LV-B1864HL 1/2" 1/4" 5 15 5 8
LV-B2461HL 5/8" 1/4" 5 20 5 8
LV-B2464HL
LV-B2464BL 5/8" 1/4" 5 20 5 8
LV-H246BLA0