• Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
• Auto Operation for Heating.
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +3°C
• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, lou-
ver moves as following cycle.
–16–
Intake Air temp. below 20°C over 20℃~below 21°C
Setting temp. 20°C Intake air temp. +0.5°C
21.5°C
20°C
20°C
Intake-Air temp.
Setting temp.
20.5°C
21°C