EasyManua.ls Logo

LG LW1200PR - Page 35

LG LW1200PR
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Manual 35
Troubleshooting Guide
Possible Trouble 2 The compressor does not operate.
Possible Trouble 3 The compressor always operate.
Is desired
Temp. set lower than Room
Temp.-0.5°C?
Is the voltage No.10
of IC01M 0V?
Replace IC01M.
Select the desired Temp. to lower Number.
Wait 3 Minutes.
Is the Unit for 3 minutes
delay?
Replace AC
PCB Ass'y.
Is the voltage N0.9 of
IC01M DC 12V?
Check the RY-COMP.
Check the wiring
Diagram.
NO
NO
NO
YES
YES
YES
YES
Is the wire connection of
RY-COMP OK?
Check the RY-COMP.
Connect LEAD Wire to
RY-COMP again.
NO
YES
NO

Related product manuals