Loading...
5. Trouble Shooting
- 71 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Error Diagnosis and Countermeasure Flow Chart
28
Inverter DC link high
voltage error
Inv PCB DC link voltage
supplied over 420V
1. Input voltage abnormal (L~N)
2. ODU inverter PCB damage(DC Link voltage
sensing part)
Display
code
Title Cause of error Check point & Normal condition
Is Inverter PCB assembly
Power connection normal?
Check connection from terminal block to
Inverter PCB assembly CN(L), CN(N)
Yes
Is input voltage normal ?
No
No
Yes
Is Inverter PCB Normal?
No
Replace inverter PCB assembly
Recheck power and installation
condition
Check L~N Voltage is 220V±15%