EasyManua.ls Logo

LG Multi-Inverter Type - Page 78

LG Multi-Inverter Type
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. Trouble Shooting
- 77 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Ω
41
44
45
46
65
D-pipe sensor (Inverter)
Air sensor
Condenser Pipe sensor
Suction Pipe sensor
Heat sink sensor
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Normal resistor : 200KΩ / at 25°C (Unplugged)
• Normal voltage : 4.5Vdc / at 25°C (plugged)
• Normal resistor : 10KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Normal resistor : 5KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Normal resistor : 5KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Normal resistor : 10KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
Display
code
Title Cause of error Check point & Normal condition
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 kΩ or ∞, then sensor is abnormal.
If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.