5. Trouble Shooting
- 80 -
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
61
Condenser
pipe sensor
temp. high
• Condenser pipe sensor
detected high temp.
• Check the load condition.
• Check the sensor of Condenser pipe sensor.
Display
code
Title Cause of error Check point & Normal condition
Check Point
- Check the install condition for over load.
(Refrigerant, Pipe length, Blocked, …)