Part 2 Functions & Controls
- 21 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Static pressure(mmAq)
Setting value
012
Model name
Step(Hi/Med/Lo)
8 CMM 220 215 210
7 CMM 240 235 230
6 CMM 255 250 245
10 CMM 210 85 150
9 CMM 215 190 170
8 CMM 220 200 175
14 CMM 170 150 130
13 CMM 185 165 145
12 CMM 200 180 160
AMNH096BTG0
[MB09AHL NT0]
AMNH126BTG0
[MB12AHL NT0]
AMNH186BTG0
[MB18AHL NT0]
Static pressure(mmAq)
Setting value
01234
Model name
Step(Hi/Med/Lo)
8.5 CMM 75 84 94 104 114
7.5 CMM 69 77 88 99 110
6.5 CMM 62 71 83 95 106
9.5 CMM 82 90 99 109 118
8.5 CMM 75 84 94 104 114
7.5 CMM 69 77 88 99 110
15 CMM 90 97 105 114 122
13.5 CMM 82 90 99 109 119
11.5 CMM 75 84 93 103 114
17 CMM 110 117 125 129 -
15 CMM 100 107 115 121 127
13.5 CMM 90 97 105 114 122
AMNH09GB1A0/1
[MB09AHL N10/1]
AMNH12GB1A0/1
[MB12AHL N10/1]
AMNH18GB2A0/1
[MB18AHL N20/1]
AMNH24GB2A0/1
[MB24AHL N20/1]
E.S.P. setting value (reference)
Static pressure(mmAq) 0 2 4
Model name
Step(Hi/Med/Lo)
Setting value
10.5CMM 225 220 210
AMNH096BPA0
9CMM 245 240 230
8.5CMM 254 253 250
11.5CMM 210 200 100
AMNH126BPA0
10CMM 235 230 220
8.5CMM 254 251 245
[ Notes ]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.