Part 2 Functions & Controls
6.1.2 Heating Mode
+2°C.
+4°C.
Comp. OFF
Comp. ON Comp. OFF Comp. ON Comp. OFF
INV. Comp.
Frequency
Constant
Comp.
Low
High LowHigh Comp. OFF
Thermo
ON
Thermo
OFF
Setting
Temp.
Operating frequency of compressor depend on the load condition, The difference between the room temp. and set
temp., frequency restrictions.
If compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30 sec-
onds.
Condition of compressor turned off
- When intake air temperature reaches +4°C above the setting temperature.
Condition of compressor turned on
- When intake air temperature reaches +2°C above the setting temperature.
* Condition of indoor fan turned off
- While in compressor on : indoor pipe temp. < 20°C
- While in compressor off : indoor pipe temp. < 30°C
While in defrost control, between the indoor and outdoor fans are turned off.
Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
CST/Duct/CVT type indoor unit matched with
Universal Outdoor unit
CST/ Duct/CVT type indoor unit
matched with Single Outdoor unit/Multi
Outdoor unit/Multi V Outdoor unit
Thermo ON : +2 °C above setting temp.
Thermo OFF : +4 °C above setting temp.
Thermo ON : Setting temp.
Thermo OFF : +3 °C above setting temp.
NOTE: Some Models are different by temperature of thermo ON/OFF.