6.1.2 Heating Mode
+2°C.
+4°C.
Comp. OFF
Comp. ON Comp. OFF Comp. ON Comp. OFF
INV. Comp.
Frequency
Constant 
Comp.
Low
High LowHigh Comp. OFF
Thermo 
ON
Thermo 
OFF
Setting
Temp.
 
• Operating frequency of compressor depend on  the load condition, The difference between the room temp. and set
temp., frequency restrictions.
• If compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30 sec-
onds.
• Condition of compressor turned off
- When intake air temperature reaches +4°C above the setting temperature.
• Condition of compressor turned on
- When intake air temperature reaches +2°C above the setting temperature.
* Condition of indoor fan turned off
- While in compressor on : indoor pipe temp. < 20°C
- While in compressor off : indoor pipe temp. < 30°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
CST/Duct/CVT type indoor unit matched with 
Universal Outdoor unit 
CST/ Duct/CVT type indoor  unit
matched with Single Outdoor unit/Multi 
Outdoor unit/Multi V Outdoor unit
Thermo ON :  +2 °C above  setting temp.
Thermo OFF : +4 °C above  setting temp.
Thermo ON :  Setting temp.
Thermo OFF :  +3 °C above  setting temp.
NOTE: Some Models are different by temperature of thermo ON/OFF.