88
Multi V Ducted Indoor Units
Due to our policy of continuous product innovation, some specifications may change without notification.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONTROLS SETUP
Group Control - Method 4
The only remote controllers that support Group Control - Method 4 are the Simple Remote Controllers.
•  Two Simple Remote Controllers (maximum) are connected to one indoor unit.
•  Set only one indoor unit in a group to main; set the others to sub. If main / sub(s) are not set properly in a group application, a malfunction 
will occur. 
•  Set only one Simple Remote Controller to main; set the others to sub (IDU function 7).
•  All types of indoor units can be congured in a Group Control - Method 4 conguration.
•  A wireless remote controller can be used at the same time as a Simple Remote Controller. 
•  A dry contact and central controller can be connected at the same time (to a main indoor unit only).
•  If an error occurs at an indoor unit, the error code is displayed at the Simple Remote Controller.
•  Group Control - Method 4 supports all indoor unit functions.
Figure 83: Group Control - Method 4, Two Simple Remote Controllers Connected to One Indoor Unit.
Main
Main Sub
GND
Signa
12 V
Sub
Sub
Display Error Message
Sub
Dry Contact
(Optional)
ACP 5
AC Smart 5
LGAP Network System
Wireless 
Handheld
Controller
Simple 
Remote
Controller
Simple 
Remote
Controller