32
ENGLISH
Mode Function Option Value Action
Remarks
Content
Display1
Content
Display2
Content Display3
Content Display4
Implement Display5
Installation
Static pres-
sure com-
pensation
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Night low
noise
oFF
op1~o
p12
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Overall de-
frost
on
oFF
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
ODU ad-
dress
-
-
0~255
set
the
value
Change
the set
value
Blank
Save in
EEPROM
Snow re-
moval &
rapid defrost
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
IDU capacity
adjusting
on
oFF
Selected
the option
--
Change
the set
value
Blank
Save in
EEPROM
Target
pressure
adjusting
op1~op4
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Comfort
Operation
on
oFF
Selected
the option
--
Change
the set
value
Blank
Save in
EEPROM
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
Outdoor Units (External PCB)
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Example) Group number setting
1
st
number indicate the group number
2nd number point out indoor unit number
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
B(D) A(C)
1 F
Group Indoor unit
Setting the function
Select the mode/function/option/value using ‘’, ‘’ Button and con-
firm that using the ‘’ button after dip switch No.5 is turned on.
DIP-SW01 7 - Segment
SW01C ( : confirm)
SW02C ( : backward)
SW03C ( : forward)
SW04C (
: cancel)
SW01D (reset)
No. Display and setup Setup and Contents
1
- Operation: Turn dip S/W No.1 on.
- Display: "11" is displayed in 7-SEG
2
- Operation: Turn dip S/W No.1 on.
- 7-SEG disappeared
7-SEG SW01M
7-SEG SW01M
No. Display and setup Setup and Contents
1
- Operation: more than 2 dip switches
turned on.
- Display: "Er" is displayed in 7-SEG
7-SEG SW01M
ROTARY 01 ROTARY 02
0
0
The connected port number of HR
unit
The connected HR unit number
The auto addressing number of in-
door unit (digit of 1)
The auto addressing number of in-
door unit (digit of 10)
No. of Indoor unit.
No. of HR unit branch.
No. of HR unit.
ROTARY 01 ROTARY 02
7 segment
0
0
CAUTION
• Waiting for 80seconds after power on.
• The zoning information and Master IDU information remove from
EEPROM after Auto-addressing.
• If there is installed the central control, it is impossible setting of
Master IDU in zoning.
!
Setting method of Master indoor unit in zoning
1 Turn dip switch 5,6,10 on at system off.
2 Set the left Ratary switch for HR unit.(Rotary switch No. "0" ‘ HR
unit No. "1")
3 Set the right Ratary switch for IDU unit.(Rotary switch No. "0" ‘ HR
unit branch No. "1")
4 Display the Master IDU No. of the HR unit on 7segment.(Default
display is "00" on 7segment)
5 Press the black button.(The IDU No. increase every 1 second in the
zoning )
6 Set the Master IDU(Press the red button during 1.5seconds stop
twinkling)
Method of checking the pipe detection result
at outdoor unit
1 Wait for 5 minutes, after Pipe detection is completed.
2 Turn on the No.10,14,16 DIP S/W of SUB PCB at master unit
3 Check the data on 7- segment, switching rotary 01,02.
Identification of Manual Valve ID (Address)
Example of checking valve address
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)

Table of Contents