Setting and using method
Installation Manual 11
ENGLISH
3. Setting the desired temperature
n When setting the desired temperature of the Dry Contact For
Setback
: When operating the indoor unit, set the desired temperature according to the TEMP_SW setting.
When the indoor unit is unlocked, the desired temperature can be reset by other controller
1) Turn on the TEMP_SETTING switch of SETTING_SW.
2) Use the TEMP_SW to set the temperature as shown below.
n When not using the desired temperature setting of Dry Con-
tact For Setback
1) Turn off the TEMP_SETTING switch of SETTING_SW.
Ú When operating the indoor unit initially with Dry Contact For Setback, set the desired temperature to
18°C.
SETTING_SW
SETTING_SW
0 1 2 3 4 5 6 7
18 19 20 21 22 23 24 25
Desired temperature setting table
TEMP SW
setting
Temperature
setting(°C)
8 9 A B C D E F
26 27 28 29 30 30 30 30
TEMP SW
setting
Temperature
setting(°C)