EasyManuals Logo

LG PDRYCB400 User Manual

LG PDRYCB400
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Setting and using method
Installation Manual 11
ENGLISH
3. Setting the desired temperature
n When setting the desired temperature of the Dry Contact For
Setback
: When operating the indoor unit, set the desired temperature according to the TEMP_SW setting.
When the indoor unit is unlocked, the desired temperature can be reset by other controller
1) Turn on the TEMP_SETTING switch of SETTING_SW.
2) Use the TEMP_SW to set the temperature as shown below.
n When not using the desired temperature setting of Dry Con-
tact For Setback
1) Turn off the TEMP_SETTING switch of SETTING_SW.
Ú When operating the indoor unit initially with Dry Contact For Setback, set the desired temperature to
18°C.
SETTING_SW
SETTING_SW
0 1 2 3 4 5 6 7
18 19 20 21 22 23 24 25
Desired temperature setting table
TEMP SW
setting
Temperature
setting(°C)
8 9 A B C D E F
26 27 28 29 30 30 30 30
TEMP SW
setting
Temperature
setting(°C)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG PDRYCB400 and is the answer not in the manual?

LG PDRYCB400 Specifications

General IconGeneral
BrandLG
ModelPDRYCB400
CategoryControl Unit
LanguageEnglish

Related product manuals