5. Trouble Shooting 
1.3 Error Indicator (Outdoor)
Outdoor Error
Ex) Error 21 (DC Peack)
◑ : 
A light on the display panel is blink.
Error
Code 
Contents 
LED01G/M
(Red) 
LED02G/M
(Green) 
case of Error 
Outdoor
Status 
21 DC Link Peak (IPM Fault) 
2times ◑ 1times ◑
Over Rated Current 
Off 
22 CT 2 (Max CT) 
2times ◑ 2times ◑
Input Over Current 
Off 
23
DC Link Low Volt.
2times ◑ 3times ◑
DC Link Volt is below 140Vdc
Off 
DC Link High Volt. 
DC Link Volt is above 420Vdc 
25 Low Voltage/Over Voltage 
2times ◑ 5times ◑
Abnormal AC Volt Input 
Off 
26 DC Compressor Position Error 
2times ◑ 6times ◑
Compressor Starting Fall Error 
Off 
27 PSC/PFC Fault Error 
2times ◑ 7times ◑
Over Inverter PCB input current 
Off 
29 COMP Over Current 
2times ◑ 9times ◑
Over Inverter Compressor Current 
Off 
32 D-Pipe High 
3times ◑ 2times ◑
D-Pipe Temp. High 
Off 
35 Low Pressure Error 
3times ◑ 5times ◑
Excessive decrease of Low Pressure 
Off 
39 Communication Error
3times ◑ 9times ◑
Communication Error Between PFC
Micom and INV Micom
Off 
40 CT Sensor (Open/Short) 
4times ◑
○
CT Circuit Malfunction 
Off 
41 INV. D-Pipe Th Error 
4times ◑ 1times ◑
Open/Short 
Off 
43 High Pressure Sensor Error 
4times ◑ 3times ◑
Open/Short 
Off 
44 Outdoor Air Th Error 
4times ◑ 4times ◑
Open/Short 
Off 
45 Cond. Mid-Pipe Th Error 
4times ◑ 5times ◑
Open/Short 
Off 
46 Suction Pipe Th Error 
4times ◑ 6times ◑
Open/Short 
Off 
48 Cond. Out-Pipe Th Error 
4times ◑ 8times ◑
Open/Short 
Off 
51 Capacity Over  
5times ◑ 1times ◑
Over combination 
Off 
53 Signal Error (Indoor <-> Outdoor) 
5times ◑ 3times ◑
Communication Poorly 
Off 
54 3-Phase Wrong wiring
5times ◑ 4times ◑
3-Phase Wrong Wring of Outdoor Unit
(Reverse Phase/Omission of Phase)
Off 
60 EEPROM Check Sum Error 
6times ◑
○
Check Sum Mismatching 
Off 
61 Cond. Pipe Th High 
6times ◑ 1times ◑
Cond. Temp. High 
Off 
62 Heaksink Th High 
6times ◑ 2times ◑
Heatsink Temp. High 
Off 
65 Heaksink Th Error 
6times ◑ 5times ◑
Open/Short 
Off 
67 Outdoor BLDC Fan Lock 
6times ◑ 7times ◑
Outdoor Fan is not operation 
Off 
73 PFC Fault Error(S/W)
7times ◑ 3times ◑
Over Current of Outdoor Unit PFC
Off