- 5 -
Ensure the cable colours (Red for +ve, Black for -ve) are correctly installed at the
circuit breakerincorrect connection of polarity between battery and inverter will
void any warranties
Connect the cables Red to Terminal D and Black to Terminal E of the battery
Do not close Circuit Breaker at this time
Connect the BMS cable from the Inverter to Socket C on the battery. If required to
extend the length of the cable, the Installer will need to provide an extension cable
with Male and Female RJ45 connectors using CAT5 ethernet cable recommended
Shielded CAT5 if outdoors.
Turn on the Battery using switch A on top right of battery – LED lights will indicate
operation.
Close the DC breaker switch
Observe overall system for at least 60 seconds to ensure Inverter is operating
correctly and review ALL settings on the Inverter for completeness.