Distance to inflammable material
When the fireplace insert is mounted in an existing brick fireplace, the
requirements for distance to inflammable material and fireproofing on the floor
will usually be in order.
If it is a matter of a new building, reference is made to any local regulations on
fireproofing etc. You may contact your chimney sweeper for clarification of
any issues of doubt.
350
250
3
0
0
For H570, the above distances to inflammable material shall apply, as
measured from the cabinet.
For H470, the distance behind the fireplace insert is 350mm. The distances
to the side and below are the same.
For furniture, a distance of 1.1 metres is recommended.
Distance to non-inflammable material
For non-inflammable material, no requirements apply.
The Chimney
A good chimney draught is essential for how well a fireplace insert will burn.
Note that there should be access to cleaning doors.
The working height of the chimney should typically range between 3.5 and 4.5
metres. Working height shall be understood as the distance from the fireplace
insert top to the top of the chimney.