Do you have a question about the LOVATO ELECTRIC PMVF 80 and is the answer not in the manual?
rated voltage | 100 - 240V~ / 110 - 250V= |
---|---|
operating range | 85 - 264V~ / 93.5 - 300V= |
frequency | 45 - 55Hz |
power consumption at Us 110V~ | 4.6VA 2.5W max |
---|---|
power consumption at Us 230V~ | 12.5VA 2.7W max |
power consumption at Us 110V= | 23mA 2.3W max |
operating temperature | -20.+40°C |
---|---|
storage temperature | -30.+80°C |
relative humidity | <80% (IEC/EN 60068-2-78) |
max rated voltage | 400V~ phase-to-phase 230V~ phase-to-neutral |
---|---|
measuring range phase-to-phase | 20 – 480V~ |
measuring range phase-to-neutral | 10 – 276V~ |
material | Polyamide RAL 7035 |
---|---|
degree of protection | IP40 front / IP20 housing and terminals |
fitting | 35mm rail (IEC/EN 60715) or screw-type |
Carefully read the manual before the installation or use.
This equipment is to be installed by qualified personnel, complying to current standards.
Before any maintenance operation on the device, remove all the voltages from measuring and supply inputs and short-circuit the CT input terminals.
The manufacturer cannot be held responsible for electrical safety in case of improper use of the equipment.
A circuit breaker must be included in the electrical installation of the building.
Clean the device with a soft dry cloth; do not use abrasives, liquid detergents or solvents.
The PMVF 80 equipment has been designed as an Interface Protection (IP) in accordance with VDE-AR-N 4105 and VDE V 0126-1-1 application guide.
It can be applied to all LV generation systems (photovoltaic, wind) where it is used to control the interface switch between generation system and public grid.
In the event of Interface Switch (IS) failure, it can also control a backup device to disconnect the generation system in any case.
The equipment features 4 digital inputs permitting the connection of the system to the signals provided by the network operator.
The PMVF 80 equipment is supplied already programmed and assembled. With the factory settings, it is ready for operation.
Changes to the settings are password protected, preventing tampering by unauthorised personnel.
Modular construction for DIN rail, 6 units.
LCD graphic 128x80 pixel, backlit, 4 grey levels. Display and setting buttons.
Voltage measuring inputs three-phase + neutral. Possibility of operation in the following line configurations.
2 switching relay outputs to control: OUT1: IS (Interface Switch) coil control; OUT2: backup device control.
4 contact digital inputs for: INP1: IS feedback input; INP2: R.O.C.O.F and Vector Shift monitoring function inhibition.
Optional additional measurements, via connection of external CTs: Currents; Powers; Energies supplied.
The voltage and frequency trip thresholds for which the equipment is set up according to the factory defaults are listed below.
PMVF 80 can be set to P≤50kW or P>50kW cases by specific commands available in the command menu.
Loss of mains thresholds (islanding detection): R.O.C.O.F (rate of change of frequency) Vector shift.
Used to enter or exit the various display and setup menus.
Used to scroll between screens, select from available options and change settings.
Used to scroll sub-pages, confirm selected options and switch between display modes.
The ▲ and ▼ buttons allow measurement display pages to be scrolled one at a time.
The first page displayed contains most important information in numerical and graphical form.
The next page displays an overview of the state of the Interface Protection System, showing outputs and control inputs.
Three pages with trip protection counters follow, divided into total, voltage, and frequency trip counts.
The button permits access to sub-pages (e.g., to display maximum and minimum values).
The sub-page is indicated by icons: IN, HI, AV, LO, GR.
Specify page and sub-page for automatic return after inactivity.
Program PMVF 80 so the display always remains on the last selected page.
The main menu consists of graphic icons for rapid access to measurements and settings.
Press MENU, select function with ▲/▼, press to activate.
Operate as shortcuts for quicker access to measurement pages or selected groups.
Default passwords: 1000 (user access) and 2000 (advanced access).
Two access levels: User-level access and Advanced-level access.
Press MENU, select password icon, enter password, press ✓.
Access remains enabled until disconnection, reset, or 2 minutes of inactivity.
Press MENU, select icon, press to access the Setting Parameters (setup) menu.
Use ▲/▼ to select desired menu, press to confirm.
Sub-menus: M01 GENERAL, M02 UTILITY, M03 PASSWORD, M04 IP THRESHOLDS, M05 COMMUNICATION, M06 ALARMS.
P01.01 Rated voltage: set VLN or VLL based on connection type P01.06.
P01.02/P01.03 VT primary/secondary voltage. P01.04/P01.05 CT primary/secondary current.
P01.06 Voltage connection/control: specifies system configuration.
P01.07 Rated system power: AUT calculation or manual input.
P01.09 LSP protection control output selection: OUT1, OUT3, or both.
P02.01 Language: Select between English and Italian.
P02.02-P02.05: Control LCD contrast and backlight intensity/delay.
P02.06/P02.07: Configure default page return and initial display page.
P02.08: Set the default sub-page for display return.
P03.01: Enable or disable password protection.
P03.02: Set the user-level access password.
P03.03: Set the advanced-level access password.
P04.01-P04.04: Configure voltage trip thresholds (Umax, Umin).
P04.09-P04.12: Configure frequency trip thresholds (Fmax, Fmin).
P04.21/P04.23: Set R.O.C.O.F. and Vector Shift trip thresholds.
P04.05-P04.08: Define delay times for voltage threshold trips.
P05.1.01-P05.1.05: Configure serial node address, speed, data format, stop bits, and protocol.
P05.1.06-P05.1.08: Set IP address, subnet mask, and IP port for Ethernet interface.
P05.1.09: Enable or disable the gateway function.
P06.01-P06.06: Enable or disable specific alarms (A01-A06).
Recommendation for using auxiliary feedback contact for IS, even if backup is not used.
C.01-C.03: Reset measurements, trip counters, and partial energy meters.
C.12/C.13: Restore settings to factory defaults for P≤50kW or P>50kW.
C.14/C.15: Save and reload device settings backup copy.
C.16/C.17: Temporarily disable voltage thresholds U> and U<.
C.18: Reset the event log.
IP command to IS for opening, but auxiliary contact remains closed.
IP command to IS for closing, but IS does not close or feedback contact fails.
PMVF 80 did not find required expansion modules.
Power Imbalance Limit protection LSP1 or LSP2 has tripped.
Event list provides description, time elapsed since power on, and total power on count.
Self-diagnosis checks display 'System Error Exx' for malfunctions.
Contact Technical Support and state the indicated error code for assistance.
Measures currents, powers, energies when CTs are connected and enabled via P01.04.
Active power produced (exported) shown with a minus sign, e.g. -6.5kW.
Displays energy production trends over the last 24 hours.
Carries out Power Unbalance Limit function for three-phase+neutral systems with CTs.
Trips on phase active power unbalance > 6kW for >30min or >10kW for >1min.
Programmable to open relay OUT3 or IS via OUT1, using parameters P01.09-P01.14.
Tripping highlighted by A05 and A06 alarms on the display.
Manual restoration by ▲ buttons or automatic restoration via P01.14.
PMVF 80 supports optional standard communication modules.
Modules require configuration via the M05 - COMMUNICATION MENU.
Supports Modbus RTU, ASCII, and TCP variants.
Illustrates the three-phase connection for the PMVF 80.
Shows connection to the Low Voltage Distribution Network (L1, L2, L3, N).
Specifies recommended fuses for auxiliary supply and contactor control.
Details terminal connections for S2 and auxiliary IS feedback.
Default mode is A. Mode D mirrors the IS output.
See parameter P01.16 (M01 - GENERAL MENU) for configuration.
Diagram showing the layout of all device terminals.
Provides detailed mechanical dimensions of the unit in millimeters.
Procedure for mounting the device onto a DIN rail or surface.
Procedure for removing the device from its mounting.
Explains warning symbols and waste disposal icons.
Details rated voltage, operating range, frequency, and power consumption.
Covers max voltage, measuring range, frequency, measurement type, and connection.
Details rated current, measuring range, input type, overload capacity, and burden.
Specifies number of outputs, type, voltage, endurance, and mechanical life.
Lists number of inputs, type, voltage levels, and input current.
Details operating temperature, storage, humidity, pollution, pressure, and altitude.