Bulletin T-TSX3
Specifications - Installation and Operating Instructions
Series TSX3 Digital Refrigeration Temperature Switch
The Series TSX3 Digital Temperature Switch was designed to control the
compressor, fan, and defrost in refrigeration applications. This generation of
controls has field selectable engineering units and input temperature types in order
to reduce the combination of parts that need to be stocked. A built in real time clock
is used for HACCP logging of temperature alarms caused by temperatures out of
their set limits or loss of power. The Intelligent Defrost parameters manage the
defrost cycle in order to save energy cost. The digital input can be used to remotely
trigger a defrost cycle, monitor cooler door status, or act as an external alarm. For
programming multiple units, the model TS2-K configuration key can be used to
quickly download parameter settings.
INSTALLATION
NOTE: Unit must be mounted away from vibration, impacts, water and corrosive
gases.
• Cut hold in panel 71 x 29 mm (2.80 x 1.14 in).
• Use the supplied gasket or apply silicone around the perimeter of the hole to
prevent leakage.
• Insert unit into hole from the front side of the panel.
• Slide the mounting bracket securely against the panel from the rear of the unit.
• Wiring diagram is displayed on the top of the control.
Wiring
Avoid installing the temperature probe cables and the digital input wires in close
proximity of any power cables. If the length of the probe cables is longer than 100
meters, a recalibration adjustment may be made using the P1 parameter.
SPECIFICATIONS
Probe Range:
PTC: -58 to 302°F (-50 to 150°C).
NTC: -58 to 230°F (-50 to 110°C).
Input: PTC (1000Ω @ 25°C) / NTC (10KΩ @ 25°C) Digital Input Contact.
Output: All Models SPST No Relay Resistive Load 16A, Inductive Load 5A, 10
FLA, 60 LRA @ 240 VAC; Dual Output Models also include 8A Resistive, 3A
Inductive SPDT @ 240 VAC; Three Output Models also include 8A Resistive
SPST NO @ 240 VAC, 5A Resistive SPST NO @ 240 VAC.
Horsepower Rating: 1HP @ 240 VAC.
Control Type: On/Off.
Power Requirement: 115 VAC, 230 VAC, 12 VAC/VDC, 24 VAC/DC (±10%)
depending on model.
Power Consumption: 3.6VA (115/230/24 V), 1.5VA (12V).
Accuracy: ±1% FS.
Display: 3 Digits Plus Sign.
Resolution: 0.1°.
Memory Backup: Non-Volatile Memory.
Ambient Temperature: 32 to 131°F (0 to 55°C).
Weight: 2.3 oz (65 g).
Front Protection: IP65.
Agency Approvals: CE, UL.
3 [76.20]
2-5/8 [66.74]
2-7/16 [61.98]
1-3/64
[26.67]
2-3/4 [69.85]
1-3/8
[35.08]
LOVE CONTROLS DIVISION
Phone: 219/879-8000 www.love-controls.com
DWYER INSTRUMENTS INC.
Fax: 219/872-9057 e-mail:love@love-controls.com
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46361, U.S.A.
T-TSX3:TEMPLATE 11/25/09 9:43 AM Page 1
1 Delta Park Blvd, #12 Brampton, ON L6T 5G1
Tel 905-457-6322 or 1-800-794-5883
Fax 905-457-4716 or 1-800-830-7122
sales@mod-tronic.com www.mod-tronic.com
Question and Answer IconNeed help?

Do you have a question about the Love Controls TSX3 Series and is the answer not in the manual?

Summary

Specifications

Probe Range

Specifies temperature input ranges for PTC and NTC probes.

Input Types

Details the types of digital inputs supported by the switch.

Output Relay Ratings

Describes relay types and load ratings for various models.

Power Requirements

Lists available power supply voltages for operation.

Accuracy and Display

States measurement precision, display digits, and resolution.

Environmental and Protection Ratings

Details operating ambient temperature and front protection.

Installation Guide

Panel Cutout and Sealing

Specifies required panel cutout dimensions and sealing methods.

Mounting Procedure

Describes how to physically insert and secure the unit.

Wiring Instructions

Cable Routing Guidelines

Guidance on routing probe and input wires away from power cables.

Recalibration Considerations

Mentions recalibration based on long probe cable lengths.

Parameter List - Compressor and Set Point

Set Point and Hysteresis

Defines the primary temperature control point and its deadband.

Set Point Limits

Sets the minimum and maximum allowable temperature set points.

Fan Operation Control

Controls the fan's operational mode based on temperature.

Compressor Cycle Timing

Manages minimum off-time and start intervals for the compressor.

Parameter List - Defrost Control

Defrosting Type and Temperature

Selects defrost method and sets the stop temperature.

Defrost Cycle Timing

Configures maximum defrost duration and initial delay.

Defrost Display and Return

Manages display during defrost and time to return to normal.

Intelligent Defrost Settings

Enables intelligent defrost methods for energy saving.

Parameter List - Display and Alarm

Display Configuration

Sets temperature scale, probe display, and decimal points.

Alarm Set Points

Defines high and low alarm temperature thresholds.

Alarm Inhibit Times

Sets time delays before alarms are validated after events.

Parameter List - Initial Setup

Real Time Clock Setup

Configures the device's real-time hours and minutes.

Digital Input and Factory Defaults

Assigns digital input function and resets to factory settings.

Probe Type and Relay Assignments

Selects probe type and configures relay functions.

HACCP and Display Refresh

Enables HACCP logging and sets display refresh rate.

Front Panel Operation

Set Point Adjustment

Procedure for adjusting the set point value via the keypad.

Time and Date Setup

Instructions for setting the real-time clock and date.

Parameter Programming

Accessing Programming Menus

Steps to enter programming menus using security code.

Navigating and Saving Parameters

How to scroll, view, change, and save parameter values.

Alarm Validation and Indicators

Alarm Acknowledgment

How to acknowledge an alarm condition to silence buzzer.

LED Indicator Meanings

Explanation of the status indicated by the device's LEDs.

HACCP and Defrosting Cycles

HACCP Alarm Recording

Details how the system registers and displays temperature alarms.

Defrost Cycle Scheduling

Explains how defrost cycles are scheduled and timed.

Love Controls TSX3 Series Specifications

General IconGeneral
DisplayLED
Current RatingUp to 10A
DifferentialAdjustable
TypeTemperature
InputTemperature
OutputRelay
Control ModeOn/Off
Voltage Rating120/240VAC
Contact ActionSPDT