2. Abnormal condition and solution
M. Inspection and Troubleshooting
Solution for Circuit Breaker’s abnormal condition
Type
Abnormal
Condition
Cause Solution
Temperature
Increase
Terminal unit
Overheating
Loose terminal unit tightening screw
Faulty booth bar assemble
Tightening with designated torque
Booth bar reassemble
Product
(except terminal
unit) overheating
Faulty contact to internal contactor
Current density increase by wire terminal
New product replacement
Abnormal
operation
Impossibility of
closing (ON)
Foreign substance in switch
Reclosing without reset on trip position
Remove foreign substance
Closing after reset
Impossibility of
reoperating
Impossibility of
Breaking/
OFF Impossibility
Worn out by breaking endurance New product exchange
Reset device operation fault Request after service
The coil of under voltage trip device is not excited. Applying power
Switch spring burn out and exhaustion. Replacement and mending
Bimetal corrosion and transformation Request after service
Reaching the life of switch limit New product exchange
Overheating of over current detecting element Operating after cooling
Contact meeting and fusion by excessive breaking
current
New product exchange
Fault
Current
Flow
Fault
Current
Flow
Inflow of insulation material between contact. Remove foreign substance
Conductive unit melting
New product exchange
Contact burn out (wear)
MCCB’s
Frequent
breaking
Break
On normal load
Wrong selection of product rating
(causing overheating )
No window inside panel (Causing overheating )
MCCB internal heating
Loose terminal connection unit.
New product exchange (rating
reselect )
New product exchange
Tightening terminal screw (check)
Fault operating
During motor
starting
Heating by starting current New product exchange
Overload current more than rated current flows.
(when using motor with overload or over voltage )
Rating adjustment
Instantaneous
Operation
While
Starting
Excessive starting current
Instantaneous breaking current
setting or rating adjustment
Excessive current Y starting switching
Excessive current by reversible operation
Instantaneous restarting rush current
Operation by starting current like charging current of
condenser, incandescent electric lamp flow,
charging, etc.
Motor’s Layer Short Motor mending
Abnormal current flow at the same time with closing Circuit inspection
Operating circuit fault connection
Inactivity
Operating current
of rated current
Large rated current Select low rated current
Current limit break of top fuse or incompatibility
with top circuit breaker
Protection cooperation review or
rating adjustment
Short circuit
of
Power side
Inactive operation
over rated
operating current
Dust piling up New product exchange
Switch side drop away of conductive material New product exchange