5
Altitude
MCCB is designed for operation at altitudes under 2000m. At altitudes higher than 2000m,
change the ratings upon a service condition.
2. Altitude and Insulation voltage
Clearances
When drawing the electric power supply panel, please keep the distance of Insulation
clearance between MCCB and panel as listed in table.
Type A B
Front
Connection
type
N 150 50
H 150 50
L 150 50
Minimum insulation clearance
The dimension of all charging parts should be over the minimum insulation clearance
Insulating
voltage(Ui)
Min. insulation
clearance(X min)
600V 8 mm
1000V 14 mm
B. Service condition
Unit :mm
B B
A
X X
Altitude
(m)
Item
2000 3000 4000 5000
Withstand voltage [V]
3500 3150 2500 2100
Average insulating
voltage [v]
1000 900 700 600
Max. using voltage [V]
690 590 520 460
Current compensation
constant
1 x In 0.99 x In 0.96 x In 0.94 x In