3. Rating Specification
D. Types and Ratings
Model TS1000 TS1250 TS1600
Frame (AF) 1000 1250 1600
Pole 3, 4 3, 4 3, 4
Type N H L N H N H
Rated current(A) In -5~40℃ 800, 1000 1250 1600
50℃ 800, 1000 1250 1560
65℃ 800, 1000 1240 1420
Rated insulation
voltage(V)
Ui 1000
Impulse withstand
voltage (kV)
Uimp 8
Rated voltage Ue AC50/60Hz 690
Icu (kA) Icu AC50/60Hz 220/240V 55 75 200 55 75 55 75
380/415V 50 70 150 50 70 50 70
440/460V 50 65 130 50 65 50 65
480/500V 40 50 100 40 50 40 50
660/690V 35 45 - 35 45 35 45
Service Breaking
capacity (kA)
Ics %Icu 100% 75% 100% 100% 75% 100% 75%
Short time
current(kA)
Icw AC50/60Hz 1s 25 25 12 25 25 25 25
3s - - - - - - -
Overriding instantaneous protection, kA peak 50 30 50
Isolation
Category B B A B B B B
Endurance Mechanical 10000 4000 10000 10000
Electrical 440V In/2 6000 6000 4000 5000 5000 5000 5000
In 5000 5000 3000 4000 4000 2000 2000
690V In/2 4000 4000 3000 3000 3000 2000 2000
In 2000 2000 2000 2000 2000 1000 1000
Pollution degree 3 3 3
Trip Relay N A P S
Over current Long time Ir (In x…)
Short time Isd (Ir x…)
Instantaneous Ii (In x…)
Ground Fault Ig (In x…)
Residual Earth Leakage IΔn -
Zone Selective Interlocking ZSI -
Nphase protection
Current Measurement -
Voltage Measurement - -
Indicating fault condition (LED)
Fault condition output contact -
Communication -
Fault Recording -
Event Recording - -
Dimension (mm) 3P 327 x 210 x 152.5
H x W x D 4P 327 x 280 x 152.5
Weight(kg) 3P 13
4P 16.8
Standards IEC60947-2